MSE of Canada
Ltd.
![]() |
|
Connection diagram for monitoring generator
![]() |
|
![]() |
|
![]() |
|
![]() |
|
![]() |
|
![]() |
|
![]() |
| Max. Line Voltage | 600V AC/DC | Power Requirement | 3 VA |
| Supply Voltage | 24V DC or
120 or 220V AC, 50/60 Hz |
Contact Rating | 5A, 250V AC
resistive |
| Isolation Voltage | 100 - 600V AC/DC | Isolation Time | 0.5 milliseconds |
| Factory Set Point | 1.5 / 3 Megohm | Weight (kg)/(oz) | 0.42/14.8 |
| Dimensions
WxHxL (mm)/(in) |
103 x 68 x 112
4.05 x 2.67 x 4.4 |
Meter | 3.5" panel mounting |
MHV-4600
![]() |
| Max. Line Voltage | 4.6kV AC | Control Voltage | 120 or 220 + 20%,
50/60 Hz 3 VA |
| Isolation Voltage | 24 - 300V AC/DC | Contact Rating | 5A, 250V AC
resistive |
| Isolation Time | 0.5 millisecond | Factory Set Points | 2.5 / 5 Megohm |
| Dimensions
WxHxL |
MHV
IRB |
103x68x112 mm
180x115x65 mm |
4.1x2.7x4.4 in
7.1x4.5x2.6 in |
| Weight | MHV
IRB |
0.42 kg
1.9 kg |
14.8 oz
67.1 oz |
| IRB Wire Length | Line Terminals Sense Terminal |
6 ft. 8 ft. |
1.8 m 2.1 m |
MHV-7200
![]() |
| Max. Line Voltage | 7.2kV AC | Control Voltage | 120 or 220 + 20%,
50/60 Hz 3 VA |
| Isolation Voltage | 24 - 300V AC/DC | Contact Rating | 5A, 250V AC
resistive |
| Isolation Time | 0.5 millisecond | Factory Set Points | 7 / 10 Megohm |
| Dimensions
WxHxL |
MHV
IRB |
103x68x112 mm
125Æ x 165 mm |
4.1x2.7x4.4 in
4.9Æ x 6.5 in |
| Weight | MHV
IRB |
0.42 kg
1.2 kg |
14.8 oz
42 oz |
| IRB Wire Length | Line Terminals Sense Terminal |
6 ft. 8 ft. |
1.8 m 2.1 m |
MHV-13800
![]() |
| Max. Line Voltage | 13.8kV AC | Control Voltage | 120 or 220 + 20%,
50/60 Hz 3 VA |
| Isolation Voltage | 24 - 300V AC/DC | Contact Rating | 5A, 250V AC
resistive |
| Isolation Time | 0.5 millisecond | Factory Set Points | 14 / 20 Megohm |
| Dimensions
WxHxL |
MHV
IRB |
103x68x112 mm
125Æ x 165 mm |
4.1x2.7x4.4 in
9.4Æ x 19.7 in |
| Weight | MHV
IRB |
0.42 kg
7.7 kg |
14.8 oz
17 lb |
| IRB Wire Length | Line Terminals Sense Terminal |
6 ft. 8 ft. |
1.8 m 2.1 m |
MHV-H-4600
![]() |
| Max. Line Voltage | 4.6kV AC | Control Voltage | 120 or 220 + 20%,
50/60 Hz 6 VA |
| Isolation Voltage | 24 - 300V AC/DC | Contact Rating | 5A, 250V AC
resistive |
| Isolation Time | 0.5 millisecond | Factory Set Point | 5, 2.5 Megohm |
| Dimensions
WxHxL |
MHV
IRB |
103x68x112 mm
180x115x65 mm |
4.1x2.7x4.4 in
7.1x4.5x2.6 in |
| Weight | MHV
IRB |
0.5 kg
1.9 kg |
17.6 oz
67.1 oz |
| IRB Wire Length | Line Terminals Sense Terminal |
6 ft. 8 ft. |
1.8 m 2.1 m |
MHV-H-7200-13800
![]() |
|
Parameter |
MHV-H-7200 MHV-H-13800 |
IRB-7200 |
IRB-13800 |
| Max. Line voltage | N/A | 7.2 kV AC | 13.8 kV AC |
| Control voltage |
120 or 220V + 20% 50 / 60 Hz |
N/A | |
| Control power | 6 VA | N/A | |
| Isolation voltage | 24 - 300V AC/DC | N/A | |
| Isolation time | 0.5 ms | N/A | |
|
Factory setpoints Low / High |
7 / 10 MW 14 / 20 MW |
N/A | |
| Contacts rating |
5A., 250V AC Resistive |
N/A | |
|
Dimensions (mm) WxHxL (in) |
103 x 68 x 112 4.05 x 2.67 x 4.4 |
122Æx165 4.9 Æ x 6.5 |
238Æx500 9.4Æx19.7 |
|
Weight (kg)/(oz) |
0.5 / 17.6 0.57 / 20 |
1.2 / 42 |
7.7 / 17 |
| IRB Wire Length | Line Terminals Sense Terminal |
6 ft. 8 ft. |
1.8 m 2.1 m |
![]() |
|
![]() |
|
![]() |
|